Wire size
More optionsContinuous load, wire type, raceway, temperature, terminals
Install
Wire size options
| Wire | Ampacity | Voltage drop |
|---|
Wire size by distance
| One way | Wire | Voltage drop |
|---|
| Wire | Ampacity | Voltage drop |
|---|
| One way | Wire | Voltage drop |
|---|
Conductors and short-circuit protection are sized from the table full-load current, not the nameplate (430.6(A)(1)). Overloads use the nameplate full-load current (430.6(A)(2)). Single motors, continuous duty.
Adds the circuit conductors at that size and an equipment grounding conductor sized from Table 250.122 for the conductor's 75°C ampacity.
Count every conductor in the raceway, including grounded and equipment grounding conductors (Ch. 9 Note 3).
Copper, Table 310.16. Not more than three current-carrying conductors, 86°F (30°C) ambient. Tap a row to select it.
| Size | 60°C | 75°C | 90°C | Breaker |
|---|
Only where the volume is marked or listed in Table 314.16(A) (314.16(A)(1)).
Each conductor that terminates or is spliced in the box counts once. A conductor that passes through unbroken counts once; a loop at least twice the free-conductor length in 300.16 (12 in.) counts twice (314.16(B)(1)). Don't count equipment grounding conductors here.
Enter inches as decimals or fractions: 6.5, 6 1/2, or 6-1/2.
Uses Chapter 9 Table 8 conductor resistance at 75°C and power factor 1. For large conductors on AC with a low power factor, Table 9 impedance gives a slightly higher drop.
Leave a box at 0 or blank when it doesn't apply. Inches over 12 are fine.
Transformers 1000 V and less (450.5(B)). Size the conductors with Wire size; secondary conductor length and protection follow 240.21(C).
Enter any two values. The other two fill in.
Efficiency is used only for horsepower. For sizing motor conductors and protection, use the table currents in Motor circuit, not this conversion (430.6(A)(1)).
TIA-598 color order. Buffer tubes, fibers, and ribbons all use the same 12-color sequence.
Enter a fiber number to see which buffer tube it's in and its color. The drawing outlines that tube and that fiber.
The letters printed on the jacket tell you where the cable is allowed. N = nonconductive (no metal). C = conductive (has metal strength members or armor).
Allowed anywhere, including plenum spaces above ceilings used for air return.
Vertical runs between floors and general areas. In a plenum only in metal raceway or a covered solid-bottom metal tray.
General areas on one floor. In a plenum only in metal raceway or a covered solid-bottom metal tray. In a riser only in metal raceway or a fireproof shaft.
| Pin | T568A | T568B |
|---|
Common questions on the job and at inspection, with 2026 NEC section numbers. Tap a question to open it.
As an Amazon Associate, Ampedia earns from qualifying purchases.
No questions match. Try another word.
Prototype built on 2026 NEC rules (load calculations now live in Article 120). Check which code edition and local amendments your area enforces. Motors, air-conditioning and refrigeration equipment sized by nameplate minimum circuit ampacity and maximum overcurrent protective device, and welders have their own sizing rules and aren't covered here. Values are calculated from the code rules; always confirm with the code book and the authority having jurisdiction.
© 2026 Ampedia. All rights reserved. Ampedia™ and the Ampedia logo are trademarks of Ampedia.
Acceptance. By using Ampedia you agree to these terms. If you do not agree, do not use the app.
Field aid only. Ampedia is a quick-reference and calculation aid. It is not professional engineering, design, legal, or code-compliance advice, and it is not a substitute for the National Electrical Code®, a licensed engineer, the equipment manufacturer's instructions, or the authority having jurisdiction. You are solely responsible for verifying every result and for every design, installation, and safety decision you make.
Accuracy. Results are based on the 2026 NEC as interpreted by the developer and may contain errors, omissions, or outdated information. Adopted code editions and local amendments vary by jurisdiction. Passing inspection is not guaranteed.
Safety and qualified persons. Electrical work can cause serious injury, death, fire, and property damage. Work must be performed only by qualified persons following applicable safety practices, including de-energizing and lockout/tagout and NFPA 70E where it applies. You use the app and perform any work at your own risk.
No warranty. The app is provided "as is" and "as available," without warranties of any kind, express or implied, including accuracy, completeness, merchantability, fitness for a particular purpose, and non-infringement.
Limitation of liability. To the fullest extent permitted by law, the developer and its owners are not liable for any direct, indirect, incidental, special, consequential, or punitive damages, including personal injury, death, property damage, fire, failed inspections, rework, delays, or lost profits, arising from or related to the use of, or inability to use, the app or its results, even if advised of the possibility of such damages. Where liability cannot be excluded, total liability is limited to the amount you paid for the app in the 12 months before the claim.
Indemnification. You agree to defend, indemnify, and hold harmless the developer and its owners from any claims, damages, or costs, including reasonable attorneys' fees, arising from your use of the app, your work, or your violation of these terms.
Use. Ampedia is licensed for your own personal or professional use. You may not copy, modify, decompile, redistribute, resell, or host this app, its code, its design, or its data, in whole or in part, without written permission.
Affiliate links. Some links in Ampedia are affiliate links. As an Amazon Associate, Ampedia earns from qualifying purchases made through those links, at no extra cost to you. Ampedia is not responsible for products, prices, or orders on third-party sites.
Changes. These terms may be updated. Continued use after an update means you accept the updated terms.
National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association, which does not endorse this app. Code section and table numbers are cited for reference only.