Wire size

Wire
More optionsContinuous load, wire type, raceway, temperature, terminals
Continuous load (runs 3 hours or more)
Terminals rated

Install

Wire size options

WireAmpacityVoltage drop

Wire size by distance

One wayWireVoltage drop
Show the math

    The motor

    Phase
    Motor marking

    Conductors and short-circuit protection are sized from the table full-load current, not the nameplate (430.6(A)(1)). Overloads use the nameplate full-load current (430.6(A)(2)). Single motors, continuous duty.

    Motor branch circuit

    How it got there

      Conduit fill

      Conductors

      Count every conductor in the raceway, including grounded and equipment grounding conductors (Ch. 9 Note 3).

      Smallest raceway

        Copper wire ampacity

          All sizes

          Copper, Table 310.16. Not more than three current-carrying conductors, 86°F (30°C) ambient. Tap a row to select it.

          Size60°C75°C90°CBreaker

          The box

          Only where the volume is marked or listed in Table 314.16(A) (314.16(A)(1)).

          Conductors that originate outside the box

          Each conductor that terminates or is spliced in the box counts once. A conductor that passes through unbroken counts once; a loop at least twice the free-conductor length in 300.16 (12 in.) counts twice (314.16(B)(1)). Don't count equipment grounding conductors here.

          Internal cable clamps

          Does it fit?

          How it got there

            Conduit bending

            Conduit (hand bender)

            Enter inches as decimals or fractions: 6.5, 6 1/2, or 6-1/2.

            Results

            Marks and steps

              Voltage drop

              Find
              Conductor

              Uses Chapter 9 Table 8 conductor resistance at 75°C and power factor 1. For large conductors on AC with a low power factor, Table 9 impedance gives a slightly higher drop.

              Results

              How it got there

                Calculator

                More

                Round to

                  Decimal to fraction

                  Nearest fraction

                  Leave a box at 0 or blank when it doesn't apply. Inches over 12 are fine.

                  The transformer

                  Phase

                  Transformers 1000 V and less (450.5(B)). Size the conductors with Wire size; secondary conductor length and protection follow 240.21(C).

                  Currents and overcurrent protection

                  How it got there

                    Ohm's law

                    Enter any two values. The other two fill in.

                    Amps, kW, kVA, and horsepower

                    Phase

                    Efficiency is used only for horsepower. For sizing motor conductors and protection, use the table currents in Motor circuit, not this conversion (430.6(A)(1)).

                    Results

                    Amps, kW, kVA, and horsepower

                      Color codes by breaker

                      Voltage
                      Phase

                        Phasing rules

                          Common questions on the job and at inspection, with 2026 NEC section numbers. Tap a question to open it.

                          Prototype built on 2026 NEC rules (load calculations now live in Article 120). Check which code edition and local amendments your area enforces. Motors, air-conditioning and refrigeration equipment sized by nameplate minimum circuit ampacity and maximum overcurrent protective device, and welders have their own sizing rules and aren't covered here. Values are calculated from the code rules; always confirm with the code book and the authority having jurisdiction.